XM31-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-915-HP
Firmware V2.07.0
Major Alarm OK
Minor Alarm Battery temperature probe alarm;
No SAG harness
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 121.58 V
Current 6.55 A
Power 692 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 2,738 Wh
Output
Voltage 86.59 V
Power 561 W
Apparent Power 632.97 VA
Frequency 60.03 Hz
Percent Load 48.70 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 7.31 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 45
Time Since Last Standby Event 0d 0h:00m
Time in Last Standby Event 0d 0h:00m
Total Time in Standby 151 min
Standby Events Since Reset 2
Time in Standby Since Reset 0 min
Time Since Reset 98 day(s)
Total Run Time 98 day(s)
Transformer Run Time 98 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 7.7 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 25 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2025 EnerSys. All Rights Reserved.